This website uses cookies primarily for visitor analytics. Certain pages will ask you to fill in contact details to receive additional information. On these pages you have the option of having the site log your details for future visits. Indicating you want the site to remember your details will place a cookie on your device. To view our full cookie policy, please click here. You can also view it at any time by going to our Contact Us page.

Balancing safety and network considerations in WirelessHART gas detection systems

16 April 2019

This article by Julian Yeo of United Electric Controls addresses recommended practices in implementing fixed-point gas detection across WirelessHART networks, although many of the considerations will apply across other wireless protocols. It approaches the topic through the lens of life safety at two levels — the device and the network.

Image: Shutterstock
Image: Shutterstock

Detection of toxic and combustible gas leaks is increasingly important for human and environmental protection, but fixed- point wired detectors can only monitor a limited area in a cost-effective way. Widespread adoption of the WirelessHART network protocol (IEC 62591) and recent advances in lithium battery technology, however, have made it affordable to supplement wired detection systems with wireless systems, improving plant safety and regulatory compliance.

Purpose of a gas detection system

Personnel safety drives the intent of a gas detection system design. For toxic gases such as hydrogen sulphide, emphasis should be on frequently trafficked routes and potential escape routes rather than on locating sensors all over the facility.

For combustible gases, such as methane, it is important to distinguish between gas leaks and gas accumulations. While leaks are of some concern, it is accumulations or gas clouds that pose the greatest explosion threat. Emphasis should be on detecting accumulations of sufficient size quickly so that mitigation measures can be implemented immediately. Factors such as obstructions and weather patterns come into play here but optimising for accumulation detection is largely a matter of maximising monitoring density in zones of greatest concern.

Safety device location methodologies

Gas detection layout should be executed in a way that achieves the intent of safeguarding personnel. There are several methodologies that can be employed, two of which are volumetric modelling and scenario-based modelling. Regardless of methodology, it is important to strike a balance between detection effectiveness and cost, which is mainly determined by the number of detectors deployed.

Volumetric modelling

This methodology is used for combustible gases and is based on the size of the target gas cloud. Target gas cloud size refers to the critical volume of combustible gas that if ignited would result in an explosion. Several factors affect the degree of gas explosion, including the level of congestion and confinement of the area concerned.

Volumetric modelling of the target gas cloud is widely accepted for gas detection design. According to the UK HSE publication OTO 93-002, the threshold size for a pressure- inducing explosion to occur is a 6-meter cloud of stoichiometrically-mixed methane in a partially enclosed environment. With increased congestion or confinement, it would take a smaller critical volume of gas to be present for an explosion to occur.

As a result, one of the guidelines suggests a 5-meter spacing rule between detectors to detect gas clouds before they can accumulate to a critical volume.

However, in enclosed environments, detector placement is optimised by charting the flow of gas leaks (in addition to accumulations) based on different release scenarios, including release rates and environmental conditions.

Scenario-based modelling

Scenario-based modelling considers various conditions that may affect how a gas leak migrates. The final output is usually a gas map. Gas mapping is a probability analysis that predicts the location of gas hazards and the likelihood of their occurrence. Gas maps are based on computational fluid dynamics models, which use rigorous numerical analysis and algorithms to predict flow of both liquids and gases. These mathematical calculations optimise gas detector placement, factoring in the following:

• Position in relation to assets

• Obstacle analysis

• Environmental conditions such as wind speed and direction

Several software applications (e.g. HazMap3D from MICROPACK (Engineering) Ltd.) are available to assist with gas mapping, including fluid dynamics calculations. Users would simply click on the desired locations of the detectors, enter the coordinates directly, and the detector is added with detection coverage shown. Some of these gas mapping tools come integrated with a library of detector models from various manufacturers.

Figure 1: Detection coverage mapped out using HazMap3D

(Image courtesy of MICROPACK (Engineering) Ltd., Aberdeen, Scotland)

Key:

Green = Areas where the target gas cloud will intersect with 2 devices

Orange = Areas where the target gas cloud will intersect with 1 device

Red = Areas where the target gas cloud will remain undetected

Where there is more than one detector involved, mapping tools can also indicate where the coverage intersects and trigger corresponding action from the detectors. For example, the green areas in figure 1 show where the target gas cloud will intersect with two devices, in a 2ooN voted scheme, where 2 channels (or detectors) out of N channels have to be in agreement before action is taken; the orange areas show where the target gas cloud will intersect with one device, thus generating an alarm only (1ooN) in a 2ooN voted layout; and the red areas are where the target gas cloud will remain undetected by the gas detection system.

In figure 2, the HazMap3D software models the dispersion of a gas leak 30- and 150-seconds after occurrence. The red areas indicate the presence of the combustible gas and how it has migrated after a 120-second lapse.

As a recommended practice, gas mapping should be performed at the Front-End Engineering Design (FEED) stage of the project life, right after the conceptual design or feasibility study is completed.  When using scenario-based modeling, the user must be mindful that there is no limit to the number of possible scenarios, resulting in a greater-than-necessary number of detectors implemented. This is again why it is critical to strike a cautious balance between performance and cost.

Other device level considerations

Determining the ideal sensor height is usually based on the personal knowledge and experience of operators. This can be an effective method but offers no traceability. As a rule of thumb, to detect gases that are lighter than air, such as methane or ammonia, detectors should be mounted at a higher level where the gas is likely to migrate.

For gases that are heavier than air, such as Butane and Sulphur Dioxide, detectors should typically be mounted closer to the ground, but breathing zones should also be considered. Hydrogen Sulphide (H2S), for example is a heavy gas with a breathing zone between 4 to 5 feet above ground.

Detectors should be positioned away from high pressure leak sources otherwise the gas expelled at high speeds may not be detected. Detector orientation also matters. Sensors should, for example, point downwards to prevent dust or water ingression. Where appropriate, the use of accessories such as a collecting cone can help to facilitate ambient sensing of the gases.

Designing the WirelessHART mesh network

In addition to device level recommendations suggested, there are methods to optimise connectivity with the WirelessHART network. The three key elements in a WirelessHART network are (i) WirelessHART field devices, (ii) gateways that facilitate wireless communication between the field devices and a wired connection to DCS, AMS or other host systems, and (iii) a network manager that coordinates and optimises data flow. The number and placement of field devices and gateways can influence network efficiency significantly.

Table 1: Considerations for wireless network design and layout (source: ISA-TR84.00.08-2017 Technical Report)

Table 1 summarises the many considerations involved in developing a reliable WirelessHART network design. These include deploying enough sensors on the network to maximise redundancy while not overloading the wireless channel; recognising potential barriers in the plant infrastructure; optimising location of routers; setting the range and proximity of sensors to ensure continuous signals; updating refresh intervals; managing battery life; and using layout and simulation tools. A new WirelessHART user might be overwhelmed with this list of seemingly complex considerations but in reality, implementing a WirelessHART network is both straightforward and simple.

Table 1
Table 1

Table 1 also specifies network topologies associated with each consideration, including mesh topologies in which sensors receive and transmit data from other field devices; star topologies in which sensors do not communicate with other devices; and hybrid topologies, which combine both mesh and star configurations. A mesh topology is used in WirelessHART networks.

Recommended practices for maximising network reliability

Regardless of how well-positioned the wireless gas detectors are for detecting gas clouds, they are ineffective if they cannot communicate data reliably across the wireless network via the gateway. Two factors that impact reliability significantly are redundancy and the distance between devices in the mesh network.

Maximising redundancy

For maximum redundancy, ensure that each field device has at least three neighbours within the effective range. That way, even if one or two of the primary paths becomes obstructed, there is still a redundant pathway back to the gateway via the third neighbour. These neighbouring devices can be instruments from any manufacturer, if they are WirelessHART compatible.

The FieldComm Group also recommends a minimum of five devices in a WirelessHART network. Networks will work properly with fewer than five WirelessHART devices, but they will not benefit from the intrinsic redundancy of a self-organising mesh network, which becomes more robust with the addition of more devices.  In a well-formed, well-designed network, new WirelessHART devices can be added to the interior or perimeter of the network without affecting operation or extensive consideration for design.

In scenarios in which the WirelessHART network has more than five devices, at least 25-percent should be in the effective range of the gateway to ensure proper bandwidth and eliminate pinch points. For example, in a 100-device network, 25 devices should be within effective range of the gateway. WirelessHART networks can work with as few as 10-percent of the devices in the effective range of the gateway but results will not be optimal.

Other network level considerations

The FieldComm Group, the organization responsible for advancing the WirelessHART standard, provides additional recommendations for WirelessHART implementation. To facilitate radio signal propagation, the recommended practice is to mount devices more than 1.5 feet from any vertical surface and more than 5 feet above ground. Devices should ideally be at the line-of-sight height which is equivalent to the obstruction height plus 6 feet. It is useful to note that radio signals are also affected by obstructions such as trees, foliage and building materials made from concrete and wood.

In certain subterranean or underwater scenarios, the radio signal is completely absorbed and cannot be propagated. Where it is not possible to relocate these obstacles, adding repeaters to propagate the WirelessHART signal could be a simple workaround.

To help establish the self-organising mesh quickly, it is recommended to install in the following sequence:

1. Install the gateway first so that the WirelessHART devices can connect to the gateway in parallel with gateway- host system integration. This saves commissioning time.

2. Commission the devices closest to the gateway first so that those located farther away can connect through the inner periphery of devices.

3. Allow more than four hours for the network to achieve optimal stability before verifying network operation.

In practice, a strong reliable WirelessHART network can easily be achieved as published WirelessHART network specifications are intentionally conservative to minimise installation and commissioning issues.

Effective range

Table 2
Table 2

It is recommended to locate wireless sensors as one would with wired sensors, organising them by process units within designated plant areas but within the effective range of an in- network device. When there is a clear line of sight, wireless signals can typically propagate around 750 feet, but as illustrated by table 2, obstructions can limit this range significantly.

Table 2: Effective Range of wireless connections among plant environments of various obstacle density (used with permission from the FieldComm Group, Austin, TX)

.

Marrying device and network level considerations

Gas detectors are only useful if they can protect lives. Wireless networks are only as good as its level of reliability. Where device- level considerations conflict with network level considerations, detection device considerations should get priority.

For example, volumetric gas cloud modelling may designate a congested area as prone to gas accumulations and thus in need of gas detection units. If this zone has no neighbouring WirelessHART devices and populated with concrete buildings, foliage and other potential signal obstructions, it would not be an ideal location for WirelessHART communication. In such cases the target cloud mapping should drive the location rather than the optimal network considerations.

Safety is the gas detector’s primary function and all considerations to help it fulfil its role should take precedence. The WirelessHART protocol is a self-organising, self-healing mesh network that is flexible enough not to be constrained by device considerations. In our example above, repeaters can always be added in between to strengthen the communication pathways between the gateway and the device.

WirelessHART enabled gas detectors offers flexibility to locate anywhere at anytime

Volumetric and scenario-based modelling methodologies have come a long way in identifying appropriate locations for point gas detectors. However, during the life of the plant, equipment and processes are changed and modernised, which can make the modelling analysis outdated. Additional processes with different gases used as a catalyst or gas by- product of the new process could be involved.

Even before the upgrades, the plant can change significantly from “as designed” to “as built” requiring the end user to remodel the gas detector locations, which few do after the FEED stage. Because the modelling software is smart and considers many dependent variables (e.g. environment), the result is that the number of gas detectors required would likely increase. The location of the gas detectors would also change after operating the plant for a time. For example, using data from personal detectors, accidents, and near miss accidents, operators can identify unprotected areas requiring increased gas detector coverage.

Fortunately, with the emergence of open source wireless (e.g. WirelessHART) gas detectors, these devices can be added anywhere to the existing mesh network easily to create an instant monitoring point, even for brownfield facilities. With WirelessHART gas detectors, the total installation cost is reduced, alleviating the financial burden that comes with increasing more detectors. The competing goals of cost-effective and safe gas detection, as well as reliable network communication can now be achieved with a WirelessHART gas detector.

About the author

Julian Yeo is currently the Strategic Marketing Manager for United Electric Controls and is responsible for developing and supporting the company’s long-term strategic growth through market innovation. Prior to this, he spent several years in Product Management (Gas Detection & Hazardous Location Pressure/Temperature Switches) as well as Application Engineering where he was involved with international projects from the planning to commissioning stage. Past positions include being an executive recruiter for global Engineering, Procurement and Construction (EPC) companies.

 