This website uses cookies primarily for visitor analytics. Certain pages will ask you to fill in contact details to receive additional information. On these pages you have the option of having the site log your details for future visits. Indicating you want the site to remember your details will place a cookie on your device. To view our full cookie policy, please click here. You can also view it at any time by going to our Contact Us page.

Partial stroke system for use in SIL 3 applications

14 April 2010

The FMEDA report showed the Netherlocks partial stoke system FAITH (Fail Action Integrity Test Handling) to be very reliable, with 0 Fail Safe Detected, Fail Safe Undetected and Fail Dangerous Detected conditions recorded from the tests. For most cases, the FAITH is suitable for use in SIL3 applications.

Partial stroke system meets SIL 3
Partial stroke system meets SIL 3

The FAITH system makes it possible to carry out a manually-initiated partial stroke test on ESD (Emergency Shut Down) valves during normal operation, without interrupting process flow. It limits, with mechanical stops, the angle of the stroke of the valve-actuator combination to a set percentage – ensuring the ESD valve ‘works’, without actually shutting down the operation. By operating mechanically rather than relying on electronic contacts or signals, reliability and simplicity is maximised.

An FMEDA (Failure Modes, Effects, and Diagnostic Analysis) assessment has been carried out by Exida on Netherlocks’ FAITH system. The product was subject to a thorough examination according to IEC 61508 to determine Probability of Failure on Demand (PFD) statistics for this device. The failure rates of the FAITH System must be added to the failure rates of the valve-actuator combination when determining the PFD AVG and Safe Failure Fraction (SFF) for the final element.


Contact Details and Archive...

Print this page | E-mail this page