This website uses cookies primarily for visitor analytics. Certain pages will ask you to fill in contact details to receive additional information. On these pages you have the option of having the site log your details for future visits. Indicating you want the site to remember your details will place a cookie on your device. To view our full cookie policy, please click here. You can also view it at any time by going to our Contact Us page.

Baseefa Ltd

US safety board says West Virginia pipeline explosion due to corrosion, lack of inspection

11 March 2014

A National Transportation Safety Board report published on March 10 concludes that the December 2012 pipeline explosion at Sissonville, West Virginia, was likely the result of corrosion and the fact that the pipeline had not been inspected in nearly 25 years. No one was injured in the huge explosion, but the NTSB said “the potential for tragedy was clearly there.”

Stock image
Stock image

On December 11, 2012, a 20-inch high-pressure natural gas pipeline running through Sissonville ruptured with so much force that a 20-foot-long segment of pipe was thrown more than 40 feet from where it had been buried. The released natural gas ignited and burned so hot that it heavily damaged the asphalt road surface on an interstate highway, destroyed three homes, and melted the siding on houses hundreds of feet from the rupture site.

"Remarkably, no lives were lost in this accident but the potential for tragedy was clearly there," NTSB Chairperson Deborah A.P. Hersman said in a news release.

"Inspection and testing improve the chances of locating defects early, and reduce the probability of a catastrophic failure which can have devastating results."

The NTSB determined corrosion on the outside of the 20-inch diameter pipe wall, caused by deteriorating coating and "ineffective cathodic protection" led to the break in the pipe, which had not been inspected since 1988.

As a result of this accident investigation, the NTSB issued three safety recommendations to the Columbia Gas Transmission Corporation and one to the Pipeline and Hazardous Materials Safety Administration, according to the news release.

The NTSB said it took the pipeline controller more than 10 minutes to recognise that a rupture had occurred despite the series of alerts he was receiving that indicated that the pressure in the pipeline had begun to decay. The shutdown was only initiated after a controller from another pipeline company reported a possible rupture to the CGTC control centre.

Following the rupture, more than an hour passed before the pipeline operator's field personnel were able to shut down the supply of natural gas to the broken pipe. More than 76 million cubic feet of natural gas was released and burned, which exacerbated the property damage caused by the accident. The NTSB said that had the pipeline been equipped with automatic shutoff valves, they would have shortened the duration of the gas-fed fire.

A 30-square-foot area of the ruptured pipeline was found to have suffered from severe external corrosion that reduced the thickness of the pipeline wall to only about 30 percent of what the pipe originally had when it was installed in 1967.

The ruptured pipe was the smallest diameter of a group of three CGTC pipelines, all of similar age, which traversed the immediate area. The two larger pipelines were in a "high consequence area," which required more stringent inspections. Both of those pipes were periodically examined with an inline inspection tool. The accident pipeline, however, had not been inspected or tested since 1988. The NTSB said that if it had been inspected with an inline tool, the rupture would likely have been prevented.