Liquid tight system has ATEX approved glands
23 January 2009
For hazardous areas where oil resistant electrical conduit systems are required, Kopex International offers a system that combines the ATEX certified flame HAM proof gland with EXLB oil resistant metallic conduit.
The combination is suitable for EX II 2 GD gas and dust as well as EExd IIC and EExe II applications.
The HAM ATEX approves flameproof gland range is designed to suit EXLB and EXSB conduits, and is available in brass, metal coated and stainless steel. With epoxy resin, the glands are approved for use in Zones 1, 2, 21 and 22 classifications where vapours gas or dust may be present for both EExd flameproof and EExe increased safety protection certification. The glands operate within a temperature range for -60º c to +80º c and have a T6 temperature classification of +85ºc. IP66 ingress protection is also provided.
EXLB conduit is a general oil resistant product with a flame retardant PVC covering. It is approved to IEC 61386 and is IP66 and IP67 rated. Conduit size availability is 10mm – 63mm (¼ inch – 2 inches).
Contact Details and Archive...